Indoor Air Quality Test Singapore | IAQ Testing Services
Indoor Air Quality Testing Singapore. Good indoor air quality improves the personal well-being and health of your employees. So, there is no doubt that premises with good quality air are more productive workplaces.
Qsafe Pte Ltd offers an indoor air quality testing service that gives you peace of mind, knowing you are providing a safe and healthy working environment for your people
Legislation
Indoor Air Quality Audit In Singapore, IAQ within buildings is regulated by the Workplace Safety and Health (Approved Codes of Practice) Notification 2011 – SS 554: Code of Practice for Indoor Air Quality for air-conditioned buildings. It specifies the indoor air quality that is acceptable to building occupants and minimizes the potential of adverse health effects.
Lighting design & SS 531:2006 :
S: NO. | TEST PARAMETERS | LIMIT FOR ACCEPTABLE INDOOR AIR QUALITY |
1 |
Carbon Dioxide, CO2 | ≤ (700 ppm + Outdoor Level) |
2 |
Carbon Monoxide, CO | ≤ 9 ppm |
3 |
Total Volatile Organic Compounds, TVOC | ≤ 1000 ppb |
4 |
Formaldehyde, HCHO | ≤ 0.08 ppm |
5 |
Fine Suspended Particles (PM2.5) | ≤ 37.5 mg/m3 |
6 |
Respirable Suspended Particulates (PM4.0) | ≤ 50 mg/m3 |
7 |
Relative Humidity | ≤ 70 % |
8 |
Air Temperature | 23 °C – 25 °C |
9 |
Air Movement | < 0.30 m/s |
10 |
Ozone Test | ≤ 0.05 ppm |
11 |
Total Bacteria Count | ≤ 1000 cfu/m3 |
Competent personnel to Assess Indoor Air Quality Test
The personnel who measuring the Indoor Air Quality shall be competent. The competency required for Indoor Air Quality in Singapore is as follows:
- Shall pass the WPH-WSH-5065-1.1 Indoor Air Quality Management-5.
- Shall know how to handle IAQ meter and record the readings
QSafe Pte Ltd provide the most competent personnel to perform the Indoor Air Quality assessment.
Our IAQ assessment includes walk-through inspection, evaluation, and measurement of thermal comfort and air contaminants.
The most advanced IAQ instruments are employed to conduct the survey. The values measured shall be compared against the maximum threshold limits set by the Singapore Standard SS 554-+A1 : 2016:2021.